beckhoff — 11.2.3.1 Hilscher CIFxx-IBM

Reference | I/O Devices Delete Device... Removes the CIF40-IBSM fieldbus card and all subsidiary elements from the I/O configuration. Online Reset Initiates an online reset on the InterBus-S. "CIF-x0 IBM" tab Address : Enter the DPRAM card address here. This address is jumped on the card and can assume the following values: from 0xC8000 to 0xEF800 in steps of 0x800 Search : Searches the computer for available CIF-40 cards (only when TwinCAT is active) Cycle Ticks : Used to set the cycle time with which the InterBus-S should be served (in ms) Synchronous Mode :

The highest priority task linked with the corresponding device controls the fieldbus cycle and is thereby synchronized with the fieldbus. All other tasks are served asynchronously via corresponding buffers. Read Config : Activates loading of current Interbus device configuration, provided that a TwinCAT configuration is started in which no devices have been configured under the Interbus master card! Up to TwinCAT 2.9 Build : After TwinCAT-Start the ”Read Bus Configuration” button is enabled. Since TwinCAT 2.9 Build > 1000 : Start TwinCAT system in config mode. Select "Reload I/O Devices" and "Scan Sub Devices".

Tab ”(Online) DPRAM” See ” Online Display of DPRAM [ } 267] Input Diagnosis The CIF-40 automatically provides two input bytes which describe the status of the card and the Interbus: GlobalFlags : The individual bits have the following definitions: 0x01 = Ctrl: Parameterisation error 0x02 = W1Err: At least one faulty W1 interface 0x04 = W2Err: At least one faulty W2 interface 0x08 = SysErr: System error occurred 0x10 = Mod: At least one slave registering module error 0x20 = Rec: At least one slave requires reconfiguration EventError : This value is dependent upon the GlobalFlags: TwinCAT 2 147 Version: 1.7