Reference | I/O Devices In the case of W1Err, W2Err, Mod or Rec the number of the affected slaves is displayed. The following conditions apply otherwise:
= 101, SysErr difference between configuration list and structure present = 103, SysErr network change during bus operation = 104, SysErr multiple data cycle error = 105, SysErr time monitoring error = 106, SysErr un-locatable network error = 108, SysErr no network connection = 170, Ctrl communication was not initialised = 171, Ctrl too many modules (> 112) parameterised = 172, Ctrl more modules connected than parameterised = 173, Ctrl fewer modules connected than parameterised = 174, Ctrl unsupported length code = 175, Ctrl incorrectly parameterised length code = 176, Ctrl incorrectly parameterised identity code = 177, Ctrl incorrectly parameterised installation depth = 178, SysErr user program-served watchdog out of configured time = 180, Ctrl unknown operating mode = 181, SysErr user program did not acknowledge data cycle 11.2.3.2 Hilscher CIF40-IBSM | Hilscher CIF40-IBSM The CIF40-IBM is an InterBus-S master card.
The DPRAM of the CIF40-IBSM is 2 Kbytes. There are no interrupts used. Context menu Append Box... Adds InterBus nodes ("boxes"). For an Overview [ } 315] of all currently supported Interbus devices, please see [ } 315] ... Delete Device... Removes the CIF40-IBSM fieldbus card and all subsidiary elements from the I/O configuration. Online Reset Initiates an online reset on the InterBus-S. TwinCAT 2 148 Version: 1.7