Reference | I/O Devices "CIF-40 IBSM" tab Address : Enter the DPRAM card address here. This address is jumped on the card and can assume the following values: from 0xC8000 to 0xEF800 in steps of 0x800 Search : Searches the computer for available CIF-40 cards (only when TwinCAT is active) Cycle Ticks : Used to set the cycle time with which the InterBus-S should be served (in ms) Synchronous Mode : The highest priority task linked with the corresponding device controls the fieldbus cycle and is thereby synchronized with the fieldbus. All other tasks are served asynchronously via corresponding buffers.
Tab ”(Online) DPRAM” See ” Online Display of DPRAM [ } 267] Input Diagnosis The CIF-40 automatically provides two input bytes which describe the status of the card and the Interbus: GlobalFlags : The individual bits have the following definitions: 0x01 = Ctrl: Parameterization error 0x02 = W1Err: At least one faulty W1 interface 0x04 = W2Err: At least one faulty W2 interface 0x08 = SysErr: System error occurred 0x10 = Mod: At least one slave registering module error 0x20 = Rec: At least one slave requires reconfiguration EventError : This value is dependent upon the GlobalFlags: In the case of W1Err, W2Err, Mod or Rec the number of the affected slaves is displayed.
The following conditions apply otherwise:
= 101, SysErr difference between configuration list and structure present = 103, SysErr network change during bus operation = 104, SysErr multiple data cycle error = 105, SysErr time monitoring error = 106, SysErr un-locatable network error = 108, SysErr no network connection = 170, Ctrl communication was not initialised = 171, Ctrl too many modules (> 112) parameterised = 172, Ctrl more modules connected than parameterised = 173, Ctrl fewer modules connected than parameterised = 174, Ctrl unsupported length code = 175, Ctrl incorrectly parameterised length code = 176, Ctrl incorrectly parameterised identity code = 177, Ctrl incorrectly parameterised installation depth TwinCAT 2 149 Version:
1.7