Reference | I/O Devices Port : Enter the card port address here. This address is jumped on the card and can assume the following values: from 0x100 to 0x3F8 in steps of 0x8 IBS cycle : The run-time of the Interbus is calculated approximately based on the configured devices and displayed. Synchronous Mode : The highest priority task linked with the corresponding device controls the fieldbus cycle and is thereby synchronized with the fieldbus. All other tasks are served asynchronously via corresponding buffers. " Activate_Configuration " at StartUp : Activates the loaded configuration during the TwinCAT StartUp phase (standard setting).
Can be disabled if other firmware services are to be accessed before StartUp (see System Start with Incomplete Configuration [ } 155] ). "Start_Data_Transfer" at StartUp : Starts cyclical data transfer in the Interbus at the TwinCAT system start. Read Bus Configuration : Activates loading of current Interbus device configuration, provided that a TwinCAT configuration is started in which no devices have been configured under the Interbus master card! Up to TwinCAT 2.9 Build : TwinCAT system reports an error message (0 boxes configured and x boxes awaited). The ”Read Bus Configuration” button is then enabled. This will display the previously recognised configuration in the tree.
Since TwinCAT 2.9 Build > 1000 : Start TwinCAT system in config mode. Select "Reload I/O Devices" and "Scan Sub Devices". Slave Diagnosis : Option available for system coupler only (Masters with slave interface). If seleceted, the process data provides additional two input words: SlaveDiag and SlaveDiagPara. Read Firmware Version : Reads the firmware version of the card via firmware service "Get_Version_Info" (see card‘s user manual). For newer motherboards/BIOS, it may be necessary to reserve the DPRAM area which the card will use in the computer BIOS. The corresponding setting is generally carried out in PNP-BIOS and is described as ISA Memblock.
”CFG” tab Lists the configuration framework produced based on the configured devices and which is loaded into the card at the system StartUp. Serves as an overview, particularly when the configuration is to be influenced at the run-time via ADS. Firmware services Nearly all SC/I-T firmware services can be accessed via ADS by each TwinCAT program. For this purpose, you need to assign an AMS port to the SC/I-T. This port is activated on the ”ADS” tab. The port number is specified as 0x7000 + the ID of the SC/I-T. Otherwise a PLC library is offered which gives the essential Firmware Services for Bus Control [ } 153] in a simple user form. TwinCAT 2 151 Version: 1.7