Reference | I/O Devices ”ADS” tab Use AdsReadWriteReq (see ADS documentation) to display the services in the following form: IndexGroup = 0x00010001 IndexOffset = firmware service code (e.g. 0x00000713 for Control_Active_Configuration) The number of parameters is determined automatically using Write data. The Write data are not converted by the TwinCAT into Motorola format. The user must do this if required. The result (confirmation) of the firmware service is returned in Read data. Example: Switching off a device while bus is in operation Interbus Box Tab ”CAC/CDF [ } 318] The device with the logical device number 3.1 should be switched off while the bus is in operation: IndexGroup:
0x00010001 IndexOffset: 0x00000713 (Control_Active_Configuration) Write Data : Word 0 0x0200 (device_Off in Motorola Format) Word 1 0x0100 (entry in Motorola Format) Word 2 0x0103 (3.1 in Motorola Format) The Write length is 6 bytes so that the firmware of the Parameter_Count 3 (words) is provided. Confirmation : Positive confirmation is as follows: Read Data : Word 0 0x0000 Negative confirmation is as follows: Read Data : Word 0 0xXXXX (result in Motorola Format) Word 1 0xXXXX (Add_Err_Info Motorola Format) TwinCAT 2 152 Version: 1.7