beckhoff — 11.2.5.2 Hilscher CIFxx-DNM

Reference | I/O Devices Delete Device... Removes the CIF30-DNM fieldbus card and all subsidiary elements from the I/O configuration. Online Reset Initiates an online reset on the DeviceNet. "CIF-30 DNM" tab Address : Enter the DPRAM card address here (CIF30-DNM and C104-DNM). This address is jumped/ configured on the card and can assume the following values: from 0xC8000 to 0xEE000 in steps of 0x2000 PCI Slot/Ring: (CIF50-DNM) Indicates the logical PCI slot into which the card is inserted. Search : Searches the computer for available CIFxx-CAN cards MAC ID : Enter the master node (scanner) card address here. These must not be duplicated within the network. Heartbeat :

Set the rate with which the DeviceNet card sends heartbeat messages (not supported at the present time). Baudrate : Used to set the baudrate used for DeviceNet operation. Watchdog : Watchdog, used by the DeviceNet card to monitor TwinCAT. VendorID : Gives the vendor ID with which the scanner card is identified in the network (e.g. in the Duplicate MAC ID Detection protocol) AutoClear : If you select this box, a node failure will halt the whole network. Otherwise, the system attempts to re-incorporate the node and continues operating. Synchronous Mode : The highest priority task linked with the corresponding device controls the fieldbus cycle and is thereby synchronized with the fieldbus.

All other tasks are served asynchronously via corresponding buffers. Firmware Update ... Update the CIFxx-DNM firmware version here. The currently loaded firmware version is shown in the window - in red if the TwinCAT recognises and is awaiting a more recent version. Tab ”(Online) DPRAM” See ” Online Display of DPRAM [ } 267] TwinCAT 2 188 Version: 1.7 Supported boxes Description BK5200 [} 282] Bus Coupler BK5210 [} 282] Economy Bus Couplers LC5200 [} 282] Low-Cost Bus Couplers DeviceNet Node [} 336] General DeviceNet device