Reference | I/O Devices Diagnostic Table 1: Global Flags Table 2: Error Rem Addr Table 3: ErrorEvent (for ErrorRemAddr = 255, Error inside device) TwinCAT 2 189 Version: 1.7 Error Code Description Troubleshooting 0x00 No error 0x01 Ctrl: Parameter error Check Master Parameter 0x02 AClr: Device stops the transmission to all nodes Check cabling, Reconfigure Master 0x04 NExc: at least one node has not reached the data exchange state Check ErrorRemAddr and ErrorEvent. inspect the field device indicated by ErrorRemAddr. 0x08 Fatal error because of heavy buserror Check cabling, inspect the field devices, may one node makes trouble on the bus, Check DeviceNet Voltage 0x10 Event:
transmission errors were detected Check cabling, inspect the field devices, may one node makes trouble on the bus, Check Baudrate and MAC Id 0x20 NRdy:
HOST is not ready Check TwinCAT System for general errors 0x40 Duplicate MacId detected Check Masters MacId 0x80 Duplicate MacId Test active Check Baudrate and cabling, Master is may not able to set up his Duplicate Mac Id messages Error Code Description Troubleshooting Station Number Number of faulted slave device Inspect the field device with the indicated MAC id, Check ErrorEvent Diagnoses 255 Error inside Device Check Master Parameter, Check ErrorEvent Diagnoses Error Code Description Troubleshooting 57 Duplicate MAC Id detected Check the addresses of the field devices, change Masters MAC Id 58 Master Config Error, download error of Master parameter Contact technical support 212 Failure in reading masters data base Contact technical support