Reference | I/O Devices Table 4: ErrorEvent (for ErrorRemAddr = Station Number, MacId) TwinCAT 2 190 Version:
1.7 Error Code Description Troubleshooting 30 device access timeout, device stopped communicating Inspect the field device, verify connections, check cabling 32 Device rejects access with unknown error code Check IO features of the device, check explicite access to device, check object class, instance, and attribute id 35 Device responses in allocation process with connection error Check IO features of the device, check explicite access to device, check object class, instance, and attribute id 36 Produced connection length is different to the configured one Check number of Bytes to be produced by the device, check devices IO configuration 37 Consumed connection length is different to the configured one Check number of Bytes to be consumed by the device, check devices IO configuration 38 Device service response telegram unknown Contact technical support of the device manufacturer 39 Connection already in Request Check cabling, inspect device, Master is not able to set up a connection to the device 40 Number of CAN-message data bytes in read produced or consumed size response not matches expected one Contact technical support of the device manufacturer 41 Predefined Master- / Slave Connection Set already exists Check number of Masters connected to the network, device my already in use by another master 42 Polling IO data length is different to the configured one Check number of Bytes to be produced by the field device, check field devices IO configuration, contact technical support of the device manufacturer 43 Sequence Error in fragmented polling IO transmission Inspect device, contact technical support of the device manufacturer 44 Fragment Error in fragmented pollingIO transmission Inspect device, contact technical support of the device manufacturer 45 Sequence Error in fragmented polling IO transmission Inspect device, contact technical support of the device manufacturer 46 Polling IO data length is different to the configured one Check number of Bytes to be produced by the device, check devices IO configuration, contact technical support of the device manufacturer 47 Sequence Error in fragmented Change of State / Cyclic IO transmission Inspect device, contact technical support of the device manufacturer 48 Sequence Error in fragmented Change of State / Cyclic IO transmission Inspect device, contact technical support of the device manufacturer 49 Sequence Error in fragmented Change of State IO transmission Inspect device, contact technical support of the device manufacturer 50 Change of State / Cyclic IO data length is different to the configured one Check number of Bytes to be produced by the device, check devices IO configuration, contact technical support of the device manufacturer