Reference | Boxes ”BK52x0” tab MAC Id : Sets the node ID of the DeviceNet participant (between 0 and 63). This value must comply with the value set at the Bus Coupler. Cycle Time : Sets the cycle time for the I0 connection. This value is added to the Expected Packet Rate (EPR) attributes of the DeviceNet slave and acts as a timeout monitor for IO connections. Electronic Key : Serves to check the devices within the network at the system StartUp. The electronic key is read from the devices at every system StartUp and compared with the saved configuration. Polled : Produced/Consumed: Activation of the ”Polling” operating mode, cyclical writing and reading of IO data.
Setting of the data content of the data transmitted via the polled IO connections. You can choose from digital data, analogue data or both. The selection depends upon the BK52xx terminal arrangement. Bit-Strobed : Produced/Consumed: Activation of the ”Bit Strobe” Operating Mode. With a broadcast message all nodes are requested to send their bit strobe message (up to 7 bytes input or status data). Setting of the data content of the data transmitted via the bit-strobed IO connections. You can choose between digital data or diagnostic data. Change of State / Cyclic : - Produced/Consumed: Setting of the data content of the data transmitted via the change of state/cyclical IO connections.
You can choose from digital data, analogue data or both. The selection depends upon the BK52xx terminal arrangement. - Change of State / Cyclic: Selecting the Corresponding Operating Mode - Heartbeat Rate / Scan Rate: In the "Change of State" mode the heartbeat rate gives the cycle time of the cyclical send of the lower-level (i.e. in addition to the event driven) IO data. In the ”Cyclic” operating mode the scan rate gives the cycle time of the IO data send. Inhibit time: Delay period in the ”Change of State” operating mode inserts this pre-set delay period after a change of state before the IO data send. Acknowledge Timeout:
Time before the re-send in the event of faulty acknowledgement of a change of state / cyclical message. Acknowledge Retry Limit: Maximum number of re-sends until IO connection goes into error mode. TwinCAT 2 283 Version: 1.7