Reference | Boxes K-Bus Update : Calculates the anticipated duration of a complete update of the terminal bus (according to the number of connected terminals). Input Diagnosis: Each DeviceNet fieldbus node contains one diagnostic input byte which signals the status of the current slave during the running time and can be linked, for example with the PLC. Table 10: CouplerState Table 11: BoxState Table 12: DataExchange TwinCAT 2 284 Version:
1.7 Error Code Description Troubleshooting 0x00 No error 0x01 IO Error Data exchange between coupler and terminals has faulted Check the IO error LEDs at the coupler, see error code in coupler manual 0x02 Coupler configuration error, devices non-volatile parameters are not valid Set Manufacturers Setting e.g. with KS2000 or via register communication and reset coupler 0x08 Diagnoses of analog terminals, this feature has first to be activated via KS200 or register communication Read the terminal diagnoses via explicite messages or via the Bit-Strobe Connection.
The Bit is reseted after reading of the diagnosis data 0x80 Fieldbus Error / Idle Mode Check Communication Parameter of the IO Connections. Send correct IO data, Check if the Device is in the Idle mode.
The bit is reseted if the device receives valid IO data Error Code Description Troubleshooting 0x02 Station not exists, device is not responding Inspect the device, verify connections, check cabling 0x05 Parameter fault Check explicite access to devices attributes, check object class, instance and attribute id 0x07 Configuration fault Check configuration settings of device 0x09 Device is deactivated Check master and device configuration Error Code Description Troubleshooting 0x00 No data exchange between node and master Inspect the field device, verify connections, check cabling 0x01 Data Exchange is active