Reference | Boxes Table 13: Variable "BoxState" at BK9000 couplers underneath a Virtual Ethernet Interface device:Virtual Ethernet Interface NOTICE The (" cycle ticks [ } 62] ") task time for the respective task should be selected to be so high that the value displayed at MissedCnt [ } 298] is always constant. In the event of doubt, it is better to select a slightly higher cycle time. Example: Minimum cycle time with selected protocol UDP [ } 298] : 30 ms Minimum cycle time with selected protocol TCP [ } 298] : 50 ms Table 14:
Variable "BoxState" at BK9000 couplers within an Ethernet Miniport (real-time) subnet:Ethernet Miniport (real-time) 11.3.1.8 BC9000 (Ethernet Interface) | BC9000 (Ethernet Interface) The Beckhoff BC9000 Bus Terminal Controller is to be configured in TwinCAT under a " Virtual Ethernet Interface". [ } 241] The following description explains the differences between the BC9000 and other Bus Couplers or Bus Terminal Controllers. The Ethernet Bus Terminal Controller communicates via TCP/IP or UDP (and ADS as the Application Layer on top of it)) with TwinCAT. For an Overview [ } 348] of all currently supported Ethernet Bus Terminal Controllers, please see [ } 348] ... Diagnosis Inputs:
The directly below the Busterminal Controller listed PLC Variables are described under " Data Exchange PC / Bus Terminal Controller [ } 112] ". TwinCAT 2 291 Version:
1.7 Variable Data Type Value Description BoxState UINT16 0x0000 No error 0x0001 No new Input information 0x0002 Outputs disabled (only with UDP [} 298]) 0xnn00 nn = current warning level (only with UDP [} 298]) Variable Data type Value Description BoxState UINT16 0x0000 No error 0x0001 No inputs received 0x0002 Outputs disabled 0x0004 No communication 0x0008 Old inputs 0x0010 Invalid input length (configured input process variables don't match attached bus terminals) 0x0020 Invalid output length (configured output process variables don't match attached bus terminals)