beckhoff — 11.3.1.8 BC9000 (Ethernet Interface)

Reference | Boxes Each fieldbus module contains status information which can be linked to TwinCAT (e.g. to to TwinCAT PLC). These status information are mostly identical at all Beckhoff fieldbus nodes (see CouplerState, MissedCnt )) and are described under -> " Status Information - Beckhoff Fieldbus nodes [ } 298] ". Only the input variable BoxState is specific and therefore described below. This variable can contain following values, which are described inside the below table. Additionally, each variable status is listed in the corresponding "Comment" field [ } 37] . "Bx9000" Tab Diagnosis : This checkbox is deactivated for the BC9000. 2 Byte PLC Interface :

This checkbox is deactivated for the BC9000. K-Bus Update : According to the attached Bus Terminals, the estimated K-Bus update time is calculated and displayed here. "PLC" Tab For information about this tab, see -> " Data Exchange PC / Bus Terminal Controller [ } 112] ". "IP Address" Tab For information about this tab, see -> " IP Address" Tab [ } 298] . "ADS Commands" Tab For information about this tab, see -> " ADS Command Window [ } 51] ". NOTICE The (" cycle ticks [ } 62] ") task time for the respective task should be selected to be so high that the value displayed at MissedCnt [ } 298] is always constant. In the event of doubt, it is better to select a slightly higher cycle time.

Example: Minimum cycle time with selected protocol UDP [ } 298] : 30 ms Minimum cycle time with selected protocol TCP [ } 298] : 50 ms TwinCAT 2 292 Version: 1.7 Variable Data Type Value Description BoxState UINT16 0x0000 No error 0x0001 No new Input information 0x0002 Outputs disabled (only with UDP [} 298]) 0xnn00 nn = current warning level (only with UDP [} 298])