Reference | Boxes "CAN Node" tab Node ID : Enter the general CANopen device node address here. If you select the "Automatic Adjust PDO COB IDs" box, the default identifier for the process data object can also be carried out after changing the node ID. Profile no .: After CANopen, the parameter 0x1000 "Device Type" contains the number of the device profile supported by the device in both the lowest value bytes. These are entered here and compared with the device parameter present at the system startup. If no device profile is supported, the parameter will contain the value 0. Add info :
The additional information is located in the two highest value bytes of the object directory entry 0x1000 (device type). FC510x: The target/actual configuration comparison is only done if Profile no. or Add. info (i.e. object directory entry 0x1000) is set to a value that is not null. If the expected values at the system startup do not match with the values present, the start of this node will be interrupted and a corresponding error message will appear in the Diag tab. CIFx0-CAN: The values are continuously compared (even if "0" is entered in both). If values do not match, the node start is interrupted. Guard time :
The guard time determines the interval at which the node is monitored (node guarding). 0 signifies no monitoring. Life time factor : Guard time x life time factor determines the watchdog length for the mutual monitoring of card and CANopen nodes. 0 indicates that the CANopen node is not monitoring the card. At 0 the card takes the Guard time directly as the watchdog length. FC510x: This card also supports the heartbeat protocol and firstly attempts to start this form of node monitoring on the CANopen node (write access to objects 0x1016 and 0x1017 in the object directory). If this attempt fails, guarding is activated.
The Guard time is entered as producer, heartbeat time and (guard time x lifetime factor) are entered as consumer heartbeat time. The card then transmits its heartbeat telegram with the smallest configured guard time (the guard times can be set individually for each node). Emcy COB ID . and Guard COB ID are identifiers for emergency messages or the guarding protocol. They result from the node address. Automatic PDO ... Specifies whether TwinCAT should download the PDO communications parameters to the node at the system startup. TwinCAT 2 321 Version: 1.7