Reference | Boxes FC510x: If the download of the PDO parameters fails, the card attempts to read these parameters and compares them with the configured values. It thus also supports nodes which have implemented the default identifiers as read-only values, for example. CIFx0-CAN: The PDO parameters are transmitted to the CANopen nodes, but it is tolerated if the nodes do not support these entries – only a confirmation of the SDO access is required (an SDO abort response is sufficient). Vendor ID, Product code, Serial no., Revision no. (FC510x only):
If values other than zero are entered here, these identity object entries (0x1018 in the object directory) are read at system startup and compared with the configured values. The corresponding node will only be started if the values match. It is also possible to compare a part of the value (e.g. Vendor ID and Product code) – then, only the non-desired parameters need to be set to null. Node error response (FC510x only): Stop node : After a detected node error, the node is set to "Stopped" state (NMT command "Stop remote node"). The node (according to each device profile) can then be switched to a safe state via the network status machine – SDO addressing is not possible in this mode.
No reaction : No NMT Stop remote node command after node error Node restart (FC510x only): Automatic restart: After a node error is detected, the card automatically attempts to restart the node. The start attempt is initiated by a Reset node command. Manual restart : After a node error, this node remains in error state and is not restarted automatically. You can trigger a restart via "I/O reset". Network reaction (FC510x only): No reaction: The failure of a node has no effect on the other bus devices Stop all nodes : After the failure of a node, all other previously started nodes are stopped (NMT Stop remote node command). You then need to restart the system. General CAN node (FC510x only):
If this checkbox is selected, the whole CANopen network management is disabled for this device, i.e. it is not started and monitored etc. The PDO entries are regarded as pure CAN telegrams (layer 2) and made available to the controller on an event-driven basis. CANopen terminology is retained As the CANopen terminology is retained, even for general CAN nodes, it must be noted that RxPDOs are the telegrams sent by the Fc510x and TxPDOs are the received telegrams. This option allows any CAN node to be connected to the TwinCAT, if the baud rate [ } 392] and the bit timing parameters match. The respective protocol can then be simulated within the PLC program.
It is also possible to run CANopen devices and general CAN nodes within the same network – if there are no identifier overlaps (the system structure is such that you cannot use an identifier twice). CANopen PDOs Process Data Objects [ } 382] (PDOs) are CAN telegrams which transport process data without a protocol overhead. RxPDOs are received by node, TxPDOs are sent by the node. This description is contained in the System Manager from the perspective of the configured node, i.e. RxPDOs are sent by the TwinCAT, TxPDOs are received by the TwinCAT. TwinCAT 2 322 Version: 1.7