Reference | Boxes 8. Step: Mapping This is the appropriately representation. Thus, CAN box RESET is terminated. 11.3.5.3 AX2000-B510 Axis (with cyclical CANopen interface) | AX2000-B510 Axis (with cyclical CANopen interface) The Beckhoff AX2000 drive is available with different optional Fieldbus interfaces. Besides these optional Fieldbus interfaces, the drives comes with an integrated CANopen interface already (X6). The AX2000 (from firmware revision 4.94 on, recommended is drive firmware revision 5.53 or higher) is in conjunction with the FC5101 [ } 169] resp. FC5102 [ } 169] capable of resolving the SYNC [ } 384] telegrams according to CANopen specification DS301 V4.01.
Therefore, the AX2000 can synchronously update its input and output process image. Intrduction Since TwinCAT 2.9, an AX2000-B510 can be mapped in the same way as any other NC supported drive type. Means, an axis e.g. "Axis 1" can be added to the NC task, the CAN specific drive type " AX2000-B510 Drive (CANopen) " can be selected via " Axis type" on the " Settings " tab and this can be linked to a "AX2000- B510" node, configured under I/O Devices -> FC510x (important is here, that a Beckhoff FC5101 or FC5102 is used in this case). Below description explains the AX2000-CANopen-specific settings in detail.
For further information on the AX2000 in CAN operation mode, please consult the manuals to be found under Digital compact Servo amplifier AX2000 on the Beckhoff Download page or Beckhoff Product CD. TwinCAT 2 328 Version: 1.7