beckhoff — 11.3.5.3 AX2000-B510 Axis (with cyclical CANopen interface)

Reference | Boxes "CAN Node" tab Node Id : The address of the CANopen node (in this case the CAN address of the AX2000 drive) must be assigned here. The drive internal setting of this address can be set via the AX2000 configuration software SR600 or through the ASCII - communication mode. The address given in this dialog must match the internal set drive address. Profile No.: + Add. Information : This object (0x1000) describes device type (Servo drive) and device functionality ( DS402 drive profile). It is the combination of the following: Guard Time (ms) : Watchdog-time in milliseconds. Life Time Factor : Specifies the handling of the "Guard Time". E.g.

a here entered "0" deactivates the watchdog. Default value is "3". Rest of the parameters, see: CANopen device [ } 320] Adjustments of Address and Baudrate with Drive Configuration Software The relevant settings for the CAN bus (Node Id, Baudrate,..) can be set via the basic settings of the SR600 software. By default address 1 and baudrate 500kb is set. After changing these values, a "Save to EEProm" with a following coldstart is necessary ( SAVE command with following COLDSTART ). TwinCAT 2 329 Version: 1.7 Description Value Bit Number of the device profile: Drive profile 402 (dec.) 0x192 (hex.) 0 - 15 Type: Servo drive 2 (dec.) 0x2 (hex.) 16 - 23 Mode bits: (Not shown in the dialog.

Bits are going to be masked if necessary, into the Hi-Byte of the Hi-WORD) Vendor-specific 0 24-31