beckhoff — 11.3.5.3 AX2000-B510 Axis (with cyclical CANopen interface)

Reference | Boxes If you want to read the current parameter, enter the ASCII command without parameters (e.g. ADDR ). The result is displayed in the next line. If the address is to be written, the address is appended after the ASCII command (e.g. ADDR1 ). AX2000-B510 tab This tab is used to select the operating mode for the AX2000. Two operating modes are available. Position Control: The default setting is " Position Control" . In this operating mode, the NC cyclically specifies a new position. The travel profile is generated by the TwinCAT NC. In the cycle time of the SEC task (e.g. 10 ms), position values are transmitted to the AX2000 via the CAN interface.

There are 3 controllers cascaded into each other on the AX2000 (current (65 µs), speed (250 µs), position (corresponds to the cycle time of the triggering SEC task)). The position control is handled entirely by the AX2000. The AX2000 reports the actual position back to the NC via the cyclic interface. TwinCAT 2 331 Version: 1.7