Reference | Boxes Velocity control: Optionally, " Velocity Control " can be activated. In this operating mode, the speed serves as the manipulated variable for the AX2000. This reduces the number of internal control loops of the AX2000 to 2, namely the current (65 µs) and speed (250 µs) controller. Compliance with the target position is checked in TwinCAT NC. The actual position is transmitted via the cyclic interface. Since the speed control on the TwinCAT NC requires shorter sampling times, the cycle time of the SEC task is set to 2 ms. Save:
When changing the cycle time of the triggering task (usually this is the NC SEC – task ) or when changing the operating mode (OPMODE), the "SAVE" button should always be pressed. Coldstart: If the data are stored (approx. 3 s after " SAVE " ) a cold start (" COLDSTART ") of the controller is necessary. The SAVE and COLDSTART commands can also be executed when the controller is enabled! "SDOs" tab In this tab, the CAN node can be parameterized in the start-up phase via the service data objects (SDOs). Entries with an object index in straight brackets have been generated automatically due to the updated terminal configuration.
Additional entries can be managed using "Append", "Insert", Delete" and "Edit". The SDO's are primarily used for parameterization of the CAN Node and the CAN PDOs [ } 382] . The first two entries define the properties of the TxPDO1: The RxPDO is configured in the same way. Custom SDOs Controller configuration TwinCAT 2 332 Version: 1.7 Object in- dex Sub Idx Length Value Description 0x1800 1 4 0x18B Cob ID (address for the send message of node 11) Default identifier [} 392] 0x1800 2 1 1 Transmission type [} 382]