beckhoff TwinCAT 2 — 5.1 Menu of the TwinCAT System Service

User Interface Processor time can be assigned to the TwinCAT real-time system via the linear regulator in the figure above. A time basis of one millisecond is cur-rently defined for this purpose. In the example shown, TwinCAT is as- signed a maximum of 30 % of the computer time. On a time basis of 1 ms, this means that TwinCAT has a maximum of 300 µs available each milli-second. Conversely, it means that at least 700 µs are available to Windows NT. When the TwinCAT real-time system switches to its idle task, the processor is returned to Windows NT. The bar in the linear regulator dis-plays the current utilisation level of the real-time system. The display is averaged over 256 cycles (ms).

System latency time: In this case, the current and maximum latency times in the real-time sys-tem are shown. The time by which the central system tick arrives too late is measured. The maximum time is saved until the linear regulator is actuated or until the dialog is exited. The latency time is, of course, also measured if the above dialog is not opened Message in the case of: If the set maximum time is exceeded, a once-only message is output in the window and a logbook entry is generated. Calling up the above dialog en-ables the message to be reset, so that a message is again output the next time the time is exceeded. Time basis: Time basis for calculating the percentage classification.

At present, a time basis of 1 millisecond is permanently set. Router: The TwinCAT Message Router can represent its internal memory admini-stration and port administration for diagnosis. This service can be called up via the context menu. System 16 Version: 1.2