PLC libraries | Data Types TF4110 40 Version: 2.0.3 Name Unit Value range Description iMode none INT Controller operation mode (1 = heating, 2 = cooling, 3 = heating & cooling) (see below) iReactionOnFail ure none INT Parameterizable reaction to errors (see below) fYTune none LREAL Control value during the self-tuning (normally 100%) fYStable none LREAL Control value during the settling phase (normally 0%) dwAlarmSupp none DWORD Masks out the alarms (see below) tCtrlCycleTime s TIME Controller's sampling time. In the course of the sampling time the controller re-calculates the control value. tTaskCycleTime s TIME Task cycle time. The FB is called with this time interval.
fWMin K LREAL Minimum setpoint fWMax K LREAL Maximum setpoint fWVeloPos K/s LREAL Rate of rise (of ramp) fWVeloNeg K/s LREAL Rate of fall (of ramp). fWStartUp K LREAL Setpoint at start-up tStartUp s TIME Time with the fWStartUp setpoint bStartUpRampin g none [TRUE,FALSE] Switches on ramping during the start-up phase.
fWStartUpVeloP os K/s LREAL Rate of rise (of ramp) during the start-up phase fWStartUpVeloN eg K/s LREAL Rate of fall (of ramp) during the start-up phase fYMin none LREAL Minimum value of the manipulated variable fYMax none LREAL Maximum value of the manipulated variable fYManual none LREAL Control value in manual operation fYOnFailure none LREAL Control value in case of error (parameterizable) tPWMCycleTim e s TIME Cycle time of the PWM signal tFilter s TIME Time constant of the actual value filter (first order P-T1 filter) bFilter none [TRUE,FALSE] The actual value filter is actuated if TRUE. bEnablePreCont roller none [TRUE,FALSE] Switches pre-controller on.
bEnableZones none [TRUE,FALSE] Switches open loop characteristic on until close to setpoint. bEnableCVFilter none [TRUE,FALSE] Switches on control value filter following the main controller. iFilterType none ENUM Selection of a filter type for the control value filter following the main controller (see below). iControllerType none ENUM Selection of a control algorithm (see below).
TempLow K LREAL Relative lower temperature limit in the first band TempLowLow K LREAL Relative lower temperature limit in the second band TempHigh K LREAL Relative upper temperature limit in the first band TempHighHigh K LREAL Relative upper temperature limit in the second band TempAbsoluteHi gh K LREAL Absolute upper temperature limit TempAbsoluteL ow K LREAL Absolute lower temperature limit fTuneKp none LREAL FineTuning parameters for the PID controller (only for advanced users) fTuneTn none LREAL FineTuning parameters for the PID controller (only for advanced users)