beckhoff TF4110 — 5.3.14 Error codes

PLC libraries | Data Types 5.3.13 ST_ParaController | ST_ParaController This version of the function block is obsolete. Do not use this function block anymore. TYPE ST_ParaController : STRUCT (* Main Controller parameter set *) KpMain : LREAL; TnMain : LREAL; TvMain : LREAL; TdMain : LREAL; (* Pre Controller parameter set *) KpPre : LREAL; TvPre : LREAL; TdPre : LREAL; END_STRUCT END_TYPE 5.3.14 Error codes | Error codes This version of the function block is obsolete. Do not use this function block anymore. TF4110 41 Version:

2.0.3 Name Unit Value range Description fTuneTv none LREAL FineTuning parameters for the PID controller (only for advanced users) fTuneTd none LREAL FineTuning parameters for the PID controller (only for advanced users) Name Unit Value range Description KpMain none LREAL Amplification factor for the main controller TnMain s TIME Integral action time for the main controller (I component) TvMain s TIME Derivative action time for the main controller (D component) TdMain s TIME Damping time for the main controller KpPre none LREAL Amplification factor for the pre-controller TvPre s TIME Derivative action time for the pre-controller (D component) TdPre s TIME Damping time for the pre-controller Name Description TC ERR NOERROR _ _ No error TC ERR INVALIDPARAM _ _ Invalid parameter TC ERR NO INIT _ _ _ Missing function block initialization.

TC ERR NO INFLECTION POINT _ _ _ _ No inflection was found during self-tuning. No parameters could be determined. TC ERR INVALID PARAM _ _ _ Invalid parameter TC ERR INVALID CYCLETIME _ _ _ Invalid combination of cycle times (sample times and PWM cycle times) TC ERR WRONG TU _ _ _ A valid value for the Tu parameter could not be found due to faulty or aborted self-tuning.