TwinCAT PLC Library Hydraulics - Version 1.4 — 4.4.1.1 MC_AxCtrlAutoZero_BkPlcMc (from V3.0)

PLCopen Motion Control increase by 10 V. The delta value is limited such that this ramp slope is not exceeded. In this way an excessively fast change, during which the correction would become unstable, can be avoided. Values greater than 100 seconds are recommended. A tolerance threshold is used for compensation. In this case LagAmpDx (threshold value of the I component in the position controller) is used. If the correction value is greater than or equal to the tolerance threshold and the actual velocity is greater than or equal to zero (i.e.

the remaining correction value is not already reduced), the Active function block is used and the compensation is reduced in each cycle by the delta value described. If the correction value is less than or equal to the tolerance threshold and the actual velocity is less than or equal to zero (i.e. the remaining correction value is not already reduced), the Active function block is used and the compensation is reduced in each cycle by the delta value described. If the magnitude of the correction value is smaller than the tolerance threshold, Active becomes FALSE.

If the compensation differs by more than the Threshold from the OldValue comparison value, the time measurement is reset and the current compensation is updated as a new comparison value. Otherwise, the time measurement is increased with the cycle time. In this way, the time required to accumulate a change in compensation by at least the Threshold is logged. Compensation&Timing: PLC Library Hydraulics 112 Version: 1.4