TwinCAT PLC Library Hydraulics - Version 1.4 — 5.2 Global constants (from V3.0)

Knowledge Base Also see about this 2 MC_AxStandardBody_BkPlcMc (V3.0) [ } 181] Documents about this 2 tcplcmcex_18.pro (https://infosys.beckhoff.com/content/1033/tcplcLibhydraulics30/Resources/ pro/1599851275.pro) 5.2 Global constants (from V3.0) Bit-masks for position cams These masks are to be used by the application to provide digital movement cams for bActPosCams in ST_TcHydAxRtData. Bit-masks for axis status information These masks are to be used by the application to interrogate status signals in nStateDWord in ST_TcHydAxRtData. PLC Library Hydraulics 235 Version: 1.4 Constant Description bTcHydActPosCamPos Summary of bTcHydActPosCamHigh and bTcHydActPosCamUp.

bTcHydActPosCamHigh The axis has reached the upper target position. bTcHydActPosCamUp The axis is located close to the upper target position. bTcHydActPosCamDown The axis is located close to the lower target position. bTcHydActPosCamLow The axis has reached the lower target position. bTcHydActPosCamNeg Summary of bTcHydActPosCamLow and bTcHydActPosCamDown. Constant Description dwTcHydNsDwFunctional Axis is ready for operation. dwTcHydNsDwReferenced Axis has been referenced. dwTcHydNsDwSteady Axis is not active. dwTcHydNsDwInTargRng The axis is located within a distance from the target position specified by fMonPositionRange in ST TcHydAxParam.

_ dwTcHydNsDwInTarget The axis has been located without interruption since a time specified by fMonTargetFilter within a distance from the target position specified by fMonTargetRange in ST TcHydAxParam. _ dwTcHydNsDwDontTouchProtected Reserved. Not supported. dwTcHydNsDwStopped The last movement of the axis was stopped without reaching the specified target position. dwTcHydNsDwBusy The axis is active. dwTcHydNsDwMoveUp The axis is moving in the direction of increasing positions. dwTcHydNsDwMoveDown The axis is moving in the direction of decreasing positions. dwTcHydNsDwReferencing Axis is homing. dwTcHydNsDwConstVelo The axis is moving with constant velocity.

dwTcHydNsDwExtSetpointActive The axis is controlled by an MC AxRtSetExtGenValues BkPlcMc _ _ [} 180] function block. dwTcHydNsDwStartedOver The axis was started, i.e. the last accepted command took effect while the axis was still in motion. dwTcHydNsDwControlActive Reserved. Not supported. dwTcHydNsDwErrState The axis is in an error state.