Resources ACK_INTO: A "come" alarm condition (status "INTO", alarm occurs) must be confirmed by the user. ACK_OUTOF: A "gone alarm" (status "OUTOF", alarm terminated) must be confirmed by the user. ACK_ALL: Gone and come alarm conditions must be confirmed by the user. Additionally you can enter a Comment . Entries for further alarm classes each will be added at the end of the list. Use button Delete to remove the currently selected entry from the list. Assigned actions for class : Each alarm class defined in the upper window can get assigned a list of actions, which should be performed as soon as a Alarm Event occurs.
In the list of Possible actions select one and press button ">" to get it into the field Assigned actions . This field will finally contain the selection of actions assigned to the alarm class. Via button " >> " you can add all actions at a single blow. Via " " resp.. " " you can remove one or all actions from the done existing selection. If an action is marked in the 'Assigned actions' list, via " ... " a corresponding dialog can be opened to define the desired e-mail settings, the printer settings, the process variable resp. the executable program and, if applicable, a message text. The following action types (Possible actions) are supported (for a definition of a message text see below):
TX1200 167 Version: 1.3 Action Description Settings to be done in the corresponding dialog: Save: The alarm event will be saved internally, in order to be given out e.g.in a log-file. Please regard: In this case the log-file must be defined in the configuration of the alarm group ! The settings are done in the Alarm group definition in the Alarm saving dialog Print: A message text is sent to a printer. Printer: Select one of the printers defined on the local system; Outputtext: Message text (see below) which should be printed out Message: In the current visualization of the alarm a message window will be opened showing the defined text. Message:
Message text to be displayed in the message window E-Mail: An e-mail containing the defined message will be sent. From: e-mail address of sender; To: e-mail address of recipient; Subject: any subject; Message: Message text (see below); Server: Name of the e-mail server Variable: A variable of the current program will get the alarm status resp. a message text string. Variable: Variable name: You can select project variables via the input assistant ( ):
A boolean variable will indicate the alarm states NORM =0 and INTO=1, an integer variable will indicate the alarm states NORM =0, INTO =1, ACK =2, OUTOF =4; a string variable will get the message text defined in field; Message (see below) Execute: An executable file will be started as soon as the alarm event occurs. Executable file: name of the file to be executed (e.g. notepad.exe, you can use the "..." button to get the standard dialog for selecting a file; Parameter: appropriate parameter(s) which should be attached to the call of the exe-file