Beckhoff Automation GmbH & Co. KG TX1200 — 6.5 Sampling Trace

Resources Stored trace configurations can be retrieved using the button Load . The standard window ”File open” is opened for this purpose. Please note that Save and Load in the configuration dialog only relates to the configuration, not to the values of a trace recording (in contrast to the menu commands ‘Extras’ ‘Save trace’ and ‘Extras’ ‘Load trace’). If the field Trigger Variable is empty, the trace recording will run endlessly and can be stopped by 'Extras' 'Stop Trace'. 'Extra' 'Start Trace' With this command the trace configuration is transferred to the PLC and the trace sampling is started in the PLC.

'Extra' 'Read Trace' With this command the present trace buffer is read from the PLC, and the values of the selected variables are displayed. 'Extra' 'Auto Read' With this command the present trace buffer is read automatically from the PLC, and the values are continuously displayed. If the trace buffer is automatically read, then a check is located before the menu item. 'Extra' 'Stop Trace' This command stops the Sampling Trace in the PLC. Before a new trace, the trace definition must be loaded, and the trace must be run again. Selection of the Variables to be Displayed The comboboxes to the right, next to the window for displaying curves trace variables defined in the trace configuration.

If a variable is selected from the list, then after the trace buffer has been read the variable will be displayed in the corresponding color (Var 0 green, etc.). Variables can also be selected if curves are already displayed. A maximum of up to eight variables can be observed simultaneously in the trace window. TX1200 177 Version: 1.3