Reference programming TX1200 226 Version: 1.3 Number Error Message Possible Cause 1411 Variable ' ' in the variable configuration isn't updated in any task The top level instance of the variable is not referenced by a call in any task. Thus it will not be copied from the process image. Example: Variable Configuration: VAR CONFIG _ plc prg.aprg.ainst.in AT %IB0 : _ INT; END VAR _ plc prg: _ index := INDEXOF(aprg); The program aprg is referenced but not called. Thus plc prg.aprg.ainst.in never will get _ the actual value of %IB0. 1412 Unexpected token ' ' in pragma {pragma name} You are using a pragma which is not written correctly resp. which cannot be used at this location.
See keyword 'pragma' in the this Online Help for getting help for a correction. 1413 ' ' is not a valid key for list ' '. The key will be ignored In the pragma a nonexistent parameter list is specified. Check the list name resp. have a look in the Parameter Manager for the currently available lists. Expression contains no assignment. No code was generated. The result of this expression is not used. For this reason there is no code generated for the whole expression. 1501 String constant passed as 'VAR IN OUT': ' ' must not _ _ be overwritten! The constant may not be written within the POU, because there no size check is possible. 1502 Variable ' ' has the same name as a POU.
The POU will not be called! A variable is used, which has the same name like a POU Example: PROGRAM a ... VAR GLOBAL _ a: INT; END VAR _ ... a; (* Not POU a is called but variable a is loaded.*) 1503 The POU ‘ ’ has no outputs. Box result is set to 'TRUE'. The Output pin of a POU which has no outputs, is connected in FBD or KOP. The assignment automatically gets the value TRUE.