Beckhoff Automation GmbH & Co. KG TX1200 — 7.5 Compiler Errors

Reference programming TX1200 227 Version: 1.3 Number Error Message Possible Cause 1504 ’ (‘ ’): Statement may not be executed due to the evaluation of the logical expression Eventually not all branches of the logic expression will be executed. Example: IF a AND funct(TRUE) THEN .... If a has is FALSE then funct will not be called. 1505 Side effect in ' '! Branch is probably not executed ! The first input of the POU is FALSE, for this reason the side branch, which may come in at the second input, will not be executed. 1506 Variable '%s' has the same name as a local action. The action will not be called! Rename the variable or the action. 1507 Instance ' ' has the same name as a function.

The instance will not be called. You call in ST an instance which has the same name like a function. The function will be called ! Use different names. 1550 Multiple calls of the POU ' ' in one network may lead to undesired side effects Check, whether the multiple call of this POU is really necessary. By a multiple call unwanted value overstrikes may occur. 1700 Input box without assignment. An input box is used in CFC which has no assignment. For this no code will be generated. 1750 Step ' ': the minimal time is greater than the maximal time! Open dialog 'Step attributes' for this step and correct the time definitions. (element # ):

Invalid watchexpression '%s' The visualization element contains an expression which cannot be monitored. Check variable name and placeholder replacements. 1801 ' (number): No Input on Expression ' ' possible In the configuration of the visualization object at field input a composed expression is used. Replace this by a single variable. 1802 (Element number): Bitmap ' ' was not found Make sure, that an external bitmap- file is available in that path which is defined in the visualization configuration dialog. 1803 ' '(' '): "The print action would not supported for web- and target visualization. A print action is assigned to an alarm configured in the visualization.

This will not be regarded in the Web- or Target- Visualization. 1804 ' '(' '): The font ' ' is not supported by the target. In the visualization you are using a font, which is not supported by the target system. See in the target settings, category 'Visualization' for the supported fonts. 1805 ' '(' '): 'Store trend data in PLC' should be set. You are using a visualization element for storing trend data. This however will not be regarded on the PLC, because option 'Store trend data' is not activated in the target settings, category Visualization.