Beckhoff Automation GmbH & Co. KG TX1200 — 7.5 Compiler Errors

Reference programming TX1200 234 Version: 1.3 Number Error Message Possible Cause 3456 The profibus device ' ' couldn't be created! The device file for module does not fit to the current configuration. Eventually it has been modified since the configuration has been set up or it is corrupted. 3457 Error in module description! Please check the device file of this module. 3458 The PLC-Configuration couldn't be created! Check the configuration files. Check if all required configuration and device files are available in the correct path (see defined compile directory in 'Project' 'Options' / Directories) 3460 3S CanDrv.lib has the wrong version.

_ Make sure, that the 3S CanDrv.lib which is _ included in the project is up to date. 3461 3S CanOpenMaster.lib has the wrong version. _ Make sure, that the 3S CanOpenMaster.lib _ which is included in the project is up to date. 3462 3S CanOpenDevice.lib has the wrong version. _ Make sure, that the 3S CanOpenDevice.lib _ which is included in the project is up to date. 3463 3S CanOpenManager.lib has the wrong _ version. Make sure, that the 3S CanOpenManager.lib _ which is included in the project is up to date. 3464 3S CanNetVar.lib has the wrong version. _ Make sure, that the 3S CanNetVar.lib which is _ included in the project, is up to date. 3465 CanDevice:

Sub indices have to be numerated sequentially In parameter lists used by the CanDevice the subindices must be numbered sequentially and without interruption. Check the corresponding list in the Parameter Manager. 3466 CAN network variables: No CAN controller found in the PLC configuration There are network variables configured for a CAN network (Ressources, Global Variables), but in the PLC Configuration there is no CAN Controller available. 3468 CanDevice: Update task not available in the task configuration.

The update task (used for calling the CANdevice), which is defined in the Base Settings dialog of the CANdevice in the PLC Configuration, must be configured in the Task Configuration of the project. 3469 The CanOpenMaster can not be called. Please assign a task manually. Assign a task, which should call the Master, via parameter UpdateTask in the Module parameters dialog in the PLC Configuration. 3470 Invalid name in parameter UpdateTask Open the CanMasters Module parameter dialog in the PLC Configuration. Check parameter UpdateTask. The specified task must be available in the project.

If you cannot set an appropriate task here, the device file must be checked for the corresponding value definitions for UpdateTask. No 'VAR CONFIG' for ' ' _ Insert a declaration for this variable in the global variable list which contains the 'Variable Configuration'. _ 3501 No address in 'VAR CONFIG' for ' '. _ Assign an address to this variable in the global variable list which contains the 'Variable Configuration'. _ 3502 Wrong data type for ' ' in 'VAR CONFIG _ In the global variables list which contains the ‚Variable Configuration’ the variable is declared _ with a different data type than in the POU.

3503 Wrong data type for ' ' in 'VAR CONFIG' _ In the global variables list which contains the ‚Variable Configuration’ the variable is declared _ with a different address than in the POU.