The UniStream ® CPU-for-Panel is designed to be plugged onto the back of a UniStream ® HMI Panel. The CPU-for-Panel is powered directly from the HMI Panel. Uni-I/O™ or Uni-COM™ modules may be snapped next to the CPU to create an all-in-one HMI + PLC controller with an onboard I/O configuration. You can expand the onboard I/O configuration of the all-in-one controller via a Local Expansion Kit ( 1) . Installation Guides are available in the Unitronics Technical Library at www.unitronicsplc.com .

Unitronics 1 UniStream® CPU-for-Panel Technical Specifications USC-P-B10 General I/O support Up to 2,048 I/O points Local Uni-I/O™ support (‎2) Up to 8 I/O modules with no additional power supply Up to 16 I/O modules with a Local Expansion Power Kit Local Uni-COM™ support (‎3) Up to 4 Uni-COM™ modules Note that the numbers above relate to Uni-I/O and Uni-COM modules. You can mix Uni-I/O and Uni-COM modules with Uni-I/O Wide modules, considering that 1 Uni-I/O Wide module equals 1½ Uni-I/O module. For example, the USC-P-B10 can support 10 Uni-I/O Wide and 1 Uni-I/O modules in any order, with a local Expansion Power Kit. Ladder Memory 1 MB Bit operation 0.13 µs Battery Model:

3V CR2032 Lithium battery (‎4) Battery lifetime: 4 years typical, at 25°C Battery Low detection and indication (via the HMI Panel and via System Tag). Connectors IO/COM Bus connector – internal bus interface to a Uni-I/O™, a Uni-COM™ or to the Base Unit of a Local Expansion Kit. System connector – interface to the Aux connector of the UniStream® HMI Panel Communication RS485 Voltage limits -7 to +12 VDC maximum, Common+Differential Baud rate range 1,200 – 115,200 bps Nodes Up to 32 Isolation voltage 500VAC for 1 minute Cable type Shielded twisted pair, in compliance with EIA RS485 Cable length Maximum 1,200 m (4,000 ft) Termination Set using DIP Switches (‎5) CANbus Power requirement None.

The CANbus port is internally powered. Isolation voltage 500VAC for 1 minute Cable type DeviceNet® shielded twisted pair

Page 1

9/14 UniStream ® Unitronics 2 Baud rate and maximum trunk line length (at different DeviceNet ® cable thickness) Baud rate Trunk line length Trunk line length Trunk line length (bps) (Thick cable) (Mid cable) (Thin cable) 1M 25m (82 ft) 25m (82 ft) 10m (32 ft) 500k 100m (328 ft) 100m (328 ft) 100m (328 ft) 250k 250m (820 ft) 250m (820 ft) 100m (328 ft) 125k, 100k 500m (1,640 ft) 300m (984 ft) 100m (328 ft) 50k, 20k,10k 1,000m (3,280 ft) 300m (984 ft) 100m (328 ft) Maximum drop line (stub) length The maximum cable distance from any device on a branching drop line to the trunk line is 2 m (6.5 ft) with any DeviceNet® cable thickness.

Maximum cumulative drop line (stub) length Baud rate Cumulative drop line length (bps) 1M 5m (16 ft) 500k 25m (32 ft) 250k 60m (197 ft) 125k, 100k 100m (328 ft) 50k, 20k,10k 100m (328 ft) Nodes Up to 64 Termination The trunk line must terminate at both ends with 121Ω, 1%, 1/4W terminating resistors. One CANbus termination resistor is included in every CPU-for-Panel kit.

Environmental Protection IP20, NEMA1 Operating temperature -20°C to 55°C (-4°F to 131°F) Storage temperature -30°C to 70°C (-22°F to 140°F) Relative Humidity (RH) 5% to 95% (non-condensing) Operating Altitude 2,000 m (6,562 ft) Shock IEC 60068-2-27, 15G, 11ms duration Vibration IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude, 8.4Hz to 150Hz, 1G acceleration

Page 2

CPU-for-Panel USC-P-B10 Technical Specifications Dimensions Weight 0.175 Kg (0.386 lb) Size Refer to the images below Top View Side View Unitronics Front View 3

Page 3

9/14 UniStream ® Notes 1. The Local Expansion Kit comprises a Base unit, an End unit, and a connecting cable. You must plug the Base Unit into the last element on the back of the UniStream ® HMI Panel. This may be a Uni-COM™ or Uni-I/O™ module. If the CPU-for-Panel is the only element that is plugged onto the back of the HMI Panel, plug the Base unit into it. 2. The CPU-for-Panel, without any additional power supply, can support up to 8 Uni-I/O™ or Uni- COM™ modules, either on-board the HMI panel or via a Local Expansion Kit. If more Uni-I/O™ modules are required, you must use a Local Expansion Kit with a power supply, this enables a single CPU to support up to 16 modules.

Note that the number of on-board Uni-I/O™ or Uni-COM™ modules is dependent on the HMI Panel model, please refer to the specification document of the corresponding HMI panel. 3. Uni-COM™ modules can only be mounted on an HMI panel. Uni-COM™ modules must be connected either directly to the CPU-for-Panel or to another Uni-COM™ module on the back of the HMI Panel. Please refer to the specification document of the corresponding HMI panel for the maximum amount of modules that can be phisically plugged on it. 4. When replacing the unit’s battery, make sure that the new one has environmental specifications 5. Please refer to the CPU-for-Panel installation guide.

that are similar or better than the one specified in this document. The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market. All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness for a particular purpose, or non-infringement.

Unitronics assumes no responsibility for errors or omissions in the information presented in this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this information. The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them. DOC25003-B8 04/18 Unitronics 4