Unitronics’ UniStream™ platform comprises control devices that provide robust, flexible solutions for industrial automation. This guide provides basic installation information for the UniStream™ CPU-for-Panel. Technical specifications may be downloaded from the Unitronics website. The UniStream™ platform comprises CPU controllers, HMI panels, and local I/O modules that snap together to form an all-in-one Programmable Logic Controller (PLC). Expand the I/O configuration using a Local Expansion Kit or remotely via CANbus. CPU-for-Panel CPUs are Programmable Logic Controllers (PLCs), the heart of the UniStream™ platform. The CPU-for-Panel cannot operate independently.

It must be plugged into the back of a UniStream™ HMI panel. The panel provides the CPU’s power source. The CPU-for-Panel comprises: IO/COM Bus connector for interfacing Uni-I/O™ & Uni-COM™ modules Isolated RS485 and CANbus ports Backup battery HMI Panels A high-resolution touch screen provides the operator interface for the system and the physical foundation for a PLC+HMI+I/Os all-in-one controller. Available in different dimensions The DIN-rail structure on the panel’s back is designed to physically support a CPU- for-Panel controller, Uni-I/O™ and/or Uni-COM™ modules. Each panel comprises:

AUX connector to support the CPU 1 audio-out 3.5mm jack 1 microSD slot 2 type A, USB host ports and 1 Mini-B USB device port 2 Ethernet ports, RJ45, 10/100 Mbps 1 power input connector, 12/24 VDC I/O Options Integrate I/Os into your system by using: On-board I/Os: snap onto the panel for an all-in-one configuration Local I/O via a Local Expansion Kit Remote I/O via EX-RC1 All-in-one UniLogic™ software, for hardware configuration, communications, and HMI/PLC applications, available as a free download from Unitronics web site.

Programming Software Use of this product is subject to a Unitronics Controller License Agreement, a copy of which can be found at http://unitronics.com/unistream/Agreements/UniLic1.pdf Unitronics 1 UniStream™ CPU-for-Panel User Guide USC-P-B10

Page 1

USC-P-B10 UniStream ® Before installing the device, the installer must: Read and understand this document. Verify the Kit Contents. Note that the CPU-for-Panel is intended to be installed on the back of an HMI panel. When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Danger The identified danger causes physical and property damage. Warning The identified danger could cause physical and property damage. Caution Caution Use caution. All examples and diagrams are intended to aid understanding, and do not guarantee operation. Unitronics accepts no responsibility for actual use of this product based on these examples.

Please dispose of this product according to local and national standards and regulations. This product should be installed only by qualified personnel. Failure to comply with appropriate safety guidelines can cause severe injury or property damage. Do not connect/disconnect the device when power is on. Ventilation: 10mm (0.4”) of space is required between the device top/bottom edges and the Do not attempt to use this device with parameters that exceed permissible levels. enclosure’s walls. Do not install in areas with:

excessive or conductive dust, corrosive or flammable gas, moisture or rain, excessive heat, regular impact shocks or excessive vibration, in accordance with the standards and limitations given in the product’s technical specification sheet. Do not place in water or let water leak onto the unit. Install at maximum distance from high-voltage cables and power equipment. Do not allow debris to fall inside the unit during installation. The following section is relevant to Unitronics’ products that are listed with the UL. The following models: USC-P-B10 is UL listed for Hazardous Locations. The following models: USC-P-B10 is UL listed for Ordinary Location.

UL Ratings, Programmable Controllers for Use in Hazardous Locations, Class I, Division 2, Groups A, B, C and D These Release Notes relate to all Unitronics products that bear the UL symbols used to mark products that have been approved for use in hazardous locations, Class I, Division 2, Groups A, B, C and D. Caution This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or Non- hazardous locations only. Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in accordance with the authority having jurisdiction. WARNING—Explosion Hazard—substitution of components may impair suitability for Class I, Division 2.

WARNING – EXPLOSION HAZARD – Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous. Unitronics 2 Before You Begin Alert Symbols and General Restrictions Environmental Considerations UL Compliance

Page 2

USC-P-B10 User GuideTechnical Specifications WARNING – Exposure to some chemicals may degrade the sealing properties of material used in Relays. This equipment must be installed using wiring methods as required for Class I, Division 2 as per the NEC and/or CEC. Removing / Replacing the battery When a product has been installed with a battery, do not remove or replace the battery unless the power has been switched off, or the area is known to be non-hazardous. Please note that it is recommended to back up all data retained in RAM, in order to avoid losing data when changing the battery while the power is switched off. Date and time information will also need to be reset after the procedure.

Certification UL des automates programmables, pour une utilisation en environnement а risques, Class I, Division 2, Groups A, B, C et D. Cette note fait rйfйrence а tous les produits Unitronics portant le symbole UL - produits qui ont йtй certifiйs pour une utilisation dans des endroits dangereux, Classe I, Division 2, Groupes A, B, C et D. Attention Cet йquipement est adaptй pour une utilisation en Classe I, Division 2, Groupes A, B, C et Le cвblage des entrйes/sorties doit кtre en accord avec les mйthodes D, ou dans Non-dangereux endroits seulement. de cвblage selon la Classe I, Division 2 et en accord avec l’autoritй compйtente. AVERTISSEMENT:

Risque d’Explosion – Le remplacement de certains composants rend caduque la certification du produit selon la Classe I, Division 2. AVERTISSEMENT - DANGER D'EXPLOSION - Ne connecter pas ou ne dйbranche pas l'йquipement sans avoir prйalablement coupй l'alimentation йlectrique ou la zone est reconnue pour кtre non dangereuse. AVERTISSEMENT - L'exposition а certains produits chimiques peut dйgrader les propriйtйs des matйriaux utilisйs pour l'йtanchйitй dans les relais. Cet йquipement doit кtre installй utilisant des mйthodes de cвblage suivant la norme Class I, Division 2 NEC et /ou CEC.

Retrait / Remplacement de la batterie Lorsqu'un produit a йtй installй avec une batterie, retirez et remplacez la batterie seulement si l’alimentation est йteinte ou si l’environnement n’est pas dangereux. Veuillez noter qu'il est recommandй de sauvegarder toutes les donnйes conservйes dans la RAM, afin d'йviter de perdre des donnйes lors du changement de la batterie lorsque l'alimentation est coupйe. Les informations sur la date et l'heure devront йgalement кtre rйinitialisйes aprиs la procйdure 1 CPU-for-Panel 1 CANbus terminal block 1 lithium battery, 3V, CR2032. 1 CANbus termination resistor Numbering instructions are in Uni-I/O™ & Uni-COM™ module installation guides.

1 RS485 terminal block The battery is installed; pull out plastic tab to activate it. 1 set of module numbering stickers. Unitronics 3 Kit Contents

Page 3

USC-P-B10 UniStream ® CPU-for-Panel Front and Rear View The HMI Panel including the CPU and any modules that will be installed on it Allocate space for: Opening the doors of the CPU and modules For exact dimensions, please refer to the Mechanical Dimensions shown below. Side View Front View Unitronics 4 CPU-for-Panel Diagram 1 DIN-rail clips 2 Battery pull-tab (remove during installation) 3 Battery compartment cover 4 IO/COM Bus connector, shipped covered. Leave covered when not in use. 5 RS485 connector 6 RS485 termination selection DIP switch 7 CANbus connector 8 CPU door 9 CPU connector to panel Installation Space Considerations CPU-for-Panel Mechanical Dimensions Battery:

Back-up, Installation, and Replacement