PMAC Product Guide I15 Degree/Radian Control for User Trig Functions Range: 0 .. 1 Default: 0 (degrees) Units: none This parameter controls whether the angle values for trigonometric functions in user programs (motion and PLC) and on-line commands are expressed in degrees (I15=0) or radians (I15=1). I50 Rapid Move Mode Control Range: 0 .. 1 Default: 1 Units: none This parameter determines which variables are used for speed of RAPID mode moves. When I50 is set to 0, the jog parameter for each motor (Ix22) is used. When I50 is set to 1, the maximum velocity parameter for each motor (Ix16) is used instead.

Regardless of the setting of I50, the jog acceleration parameters Ix19-Ix21 control the acceleration. I52 \ Program Hold Slew Rate Range: 0 .. 8,388,607 Default: 37,137 Units: I10 units / segmentation period This parameter controls the slew rate to a stop on a \ program hold command and the slew rate back up to speed on a subsequent R command, for all coordinate systems, provided PMAC is in a segmented move ( LINEAR or CIRCLE mode with I13>0). If PMAC is not in a segmented move (I13=0, or other move mode), the \ command acts just like an H feed hold command, with Ix95 controlling the slew rate. The units of I52 are the units of I10 (1/8,388,608 msec) per segmentation period (I13 msec).

To calculate how long it takes to stop on a \ command and to restart on the next R command, use the formula T (msec) = I10 * I13 / I52 To calculate the value of I52 for a given start/stop time, use the formula I52 = I10 * I13 / T (msec) Example: To execute a full stop in one second with the default servo update time (I10 = 3,713,707) and a move segmentation time of 10 msec, I52 should set to 3,713,707 * 10 / 1000 = 37,137. I53 Program Step Mode Control Range: 0 .. 1 Default: 0 Units: none This parameter controls the action of a STEP ( S ) command in any coordinate system on PMAC.

At the default I53 value of zero, a STEP command causes program execution through the next move, DELAY , or DWELL command in the program, even if this takes multiple program lines. When I53 is set to 1, a STEP command causes program execution of only a single program line, even if there is no move or DWELL command on that line. If there is more than one DWELL or DELAY command on a program line, a single STEP command will execute only one of the DWELL or DELAY commands. Regardless of the setting of I53, if program execution on a Step command encounters a BLOCKSTART statement in the program, execution will continue until a BLOCKSTOP statement is encountered. 102 I-Variables