User Manual of EM730 Series Inverter 107 F09.26 Detection time of PID feedback disconnection 0.000 ~ 30.000 s 0.000 ● 0x091A F09.27 PID sleep control options 0: invalid 1: sleep at zero speed 2: sleep at lower frequency limit 3:
sleep with tube sealed 0 ● 0x091B F09.28 Sleep action point 0.00-100.00 (100.00 corresponds to the PID setting feedback range) % 100.0 0 ● 0x091C F09.29 Sleep delay time 0.0 ~ 6500.0 s 0.0 ● 0x091D F09.30 Wake-up action point 0.00 ~100.00 (100.00 corresponds to the PID setting feedback range) % 0.00 ● 0x091E F09.31 Wake-up delay time 0.0 ~ 6500.0 s 0.0 ● 0x091F F09.32 Multi-segment PID setting 1 0.0 to PID setting feedback range F09.03 0.0 ● 0x0920 F09.33 Multi-segment PID setting 2 0.0 to PID setting feedback range F09.03 0.0 ● 0x0921 F09.34 Multi-segment PID setting 3 0.0 to PID setting feedback range F09.03 0.0 ● 0x0922 F09.35 Upper limit of feedback voltage lower limit of feedback voltage to 10.00 V 10.00 ● 0x0923 F09.36 Lower limit of feedback voltage 0.00 to upper limit of feedback voltage V 0.00 ● 0x0924 F09.37 Integral action option within set PID change time 0:
always calculate the integral term 1: calculate the integral term after the F09.21 set time is reached 2: calculate the integral term when the error is less than F09.38 0 Straig ht-2 ● 0x0925 F09.38 Integral within set PID change time Input deviation 0.00-100.00 % 0 ● 0x0926