sinee — 6.2Table of functional parameters

User Manual of EM730 Series Inverter 108 F09.39 Wake-up option 0: target pressure F09.01* coefficient of wake-up action point 1: wake-up action point (F09.30) 0 〇 0x0927 F09.40 Coefficient of wake-up action point 0.0~100.0 (100% corresponds to PID setting) % 90.0 ● 0x0928 F09.41 Pipeline network alarm overpressure 0.0 to pressure sensor range F09.03 % 90.0 ● 0x0929 F09.42 Overpressure protection time 0 ~ 3600 (0: invalid) s 6 ● 0x092A F09.43 PID reverse limit 0: no limit 1: limit 1 〇 0x092B F09.44 Dormation method selection 0: Follow the frequency of dormancy (F09.45) 1:

Follow the dormant movement point to sleep (F09.28) 0 〇 0x092C F09.45 Dormant frequency 0.00 ~ upper limit frequency f00.18 Hz 30.00 ● 0x092D F09.46 Pressure feedback increment 0~100 5 ● 0x092E F09.47 PID regulating dead area 0.00~600.00 Bar 0.02 ● 0x092F F10 Communication function group F10.00 Local Modbus communicatio n address 1-247; 0: broadcast address 1 〇 0x0A00 F10.01 Baud rate of Modbus communicatio n 0:4800 1:9600 2:19200 3:38400 4:57600 5:115200 1 〇 0x0A01 F10.02 Modbus data format 0: 1-8-N-1 (1 start bit + 8 data bits + 1 stop bit) 1: 1-8-E-1 (1 start bit + 8 data bits + 1 even parity check bit + 1 stop bit) 2:

1-8-O-1 (1 start bit + 8 data bits + 1 odd parity check bit + 1 stop bit) 3: 1-8-N-2 (1 start bit + 8 data bits + 2 stop bits) 0 〇 0x0A02