User Manual of EM730 Series Inverter 116 F13.03 Multi-segment torque 1 -200.0 ~ 200.0 % 0.0 ● 0x0D03 F13.04 Multi-segment torque 2 -200.0 ~ 200.0 % 0.0 ● 0x0D04 F13.05 Multi-segment torque 3 -200.0 ~ 200.0 % 0.0 ● 0x0D05 F13.06 Torque control acceleration and deceleration time 0.00 ~ 120.00 s 0.00 ● 0x0D06 F13.08 Upper frequency limit options of torque control 0: set by F13.09 1: AI1 2: AI2 3: reserved 4: reserved 5: high frequency pulse input (X5) 6: communication setting (percentage) 7:
communication setting (direct frequency) 0 〇 0x0D08 F13.09 Positive upper limit of torque control frequency 0.50 to maximum frequency F00.16 Hz 50.00 ● 0x0D09 F13.10 Upper frequency limit offset 0.00 to maximum frequency F00.16 Hz 0.00 ● 0x0D0A F13.11 Static friction torque compensation 0.0 ~ 100.0 % 0.0 ● 0x0D0B F13.12 Frequency range of static friction compensation 0.00 ~ 50.00 Hz 1.00 ● 0x0D0C F13.13 Dynamic friction torque compensation 0.0 ~ 100.0 % 0.0 ● 0x0D0D F13.18 Reverse speed limit options 0 ~ 100 % 100 ● 0x0D12 F13.19 Reverse torque control options 0 ~ 1 0 ● 0x0D13