sinee — 6.2Table of functional parameters

User Manual of EM730 Series Inverter 128 F15.56 The current reaches the hysteresis 0.0~F15.44 % 5.0 ● 0x0F38 F15.57 Torque reaches test value 0.0~300.0(100.0% corresponding to rated motor torque) % 100.0 ● 0x0F39 F15.58 The torque reaches the hysteresis ring 0.0~F15.46 % 5.0 ● 0x0F3A F15.62 PG card feedback frequency display filtering time 0~20000 ms 300 ● 0x0F3E F15.63 The speed reaches the limit of rise 0.00~Fmax Hz 30.00 ● 0x0F3F F15.64 The speed reaches filtering time 0~60000 ms 500 ● 0x0F40 F15.65 The speed reaches the limit of descent 0.00~Fmax Hz 0.00 ● 0x0F41 F15.66 Overcurrent detection level 0.1~ 300.0 (0.0: no detection; 100.0%:

corresponding to the rated current of motor) % 200.0 ● 0x0F42 F15.67 Overcurrent detection delay time 0.00 ~ 600.00 s 0.00 ● 0x0F43 F15.68 Market price 0.00 ~ 100.00 1.00 〇 0x0F44 F15.69 Power-frequen cy load factor 30.0 ~ 200.0 % 90.0 〇 0x0F45 F16 Customization function group F16.00 Industry application 0:universal model 1:water supply application 2:air compressor application 3:winding application 4:fan application 5:spindle application of machine tool 0 〇 0x1000