sinee — 7.9Multi-segment Speed and Simple PLC Parameter Group

User Manual of EM730 Series Inverter Precautions for setting: ★ The start and stop in multi-segment speed operation depends on the function code F00.02. ★ The acceleration/deceleration time in multi-segment speed operation can be controlled by the external terminal with the acceleration/deceleration time function. The direction of multi-segment speed operation is controlled by the terminals F/R and RUN. In addition to the multi-segment speed mode, it also has the simple PLC function. There are four running modes in total, as detailed in Table 7-13.

Table 7- 13 Details of PLC Running Mode ★ The last segment refers to the segment that is not set to 0, judged from the running time (F08.48) of the 15 th segment toward the 1 st segment. 229 speed 14 16 Valid Valid Valid Valid Multi-segment speed 15 F08.14 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F08.15 Simple PLC running mode 0: stop after a single run 1: stop after a limited number of cycles 2: run at the last segment after a limited number of cycles 3: continuous cycles 0 ● 0x080F F08.16 Limited number of cycles 1 ~ 10000 1 ● 0x0810 F08.15 Description 0 The inverter will be stopped after running in the last segment.

1 The inverter will run cyclically and be stopped after the set cycles. The number of cycles depends on the function code F08.16. 2 The inverter will run cyclically and keep the speed of the last segment after running in the last segment, until a stop command is received. The number of cycles depends on the function code F08.16. 3 The inverter will continue cyclic operation until a stop command is received.