sinee — 7.9Multi-segment Speed and Simple PLC Parameter Group

User Manual of EM730 Series Inverter The 16-segment speed can be provided according to the multi-segment speed control terminal, 15-segment frequency command and digital frequency setting F00.07.

Table 7- 12 Combination of Multi-segment Speed Command &Multi-segment Speed Terminal 228 F08.14 Multi-segment speed 15 0.00 to maximum frequency F00.16 Hz 50.00 ● 0x080E Segment Speed Multi- segment speed terminal 4 Multi- segment speed terminal 3 Multi- segment speed terminal 2 Multi- segment speed terminal 1 Selected frequency Corresponding function code 1 Invalid Invalid Invalid Invalid Digital frequency setting Depending on F00.07 2 Invalid Invalid Invalid Valid Multi-segment speed 1 F08.00 3 Invalid Invalid Valid Invalid Multi-segment speed 2 F08.01 4 Invalid Invalid Valid Valid Multi-segment speed 3 F08.02 5 Invalid Valid Invalid Invalid Multi-segment speed 4 F08.03 6 Invalid Valid Invalid Valid Multi-segment speed 5 F08.04 7 Invalid Valid Valid Invalid Multi-segment speed 6 F08.05 8 Invalid Valid Valid Valid Multi-segment speed 7 F08.06 9 Valid Invalid Invalid Invalid Multi-segment speed 8 F08.07 10 Valid Invalid Invalid Valid Multi-segment speed 9 F08.08 11 Valid Invalid Valid Invalid Multi- speed 10 F08.09 12 Valid Invalid Valid Valid Multi-segment speed 11 F08.10 13 Valid Valid Invalid Invalid Multi-segment speed 12 F08.11 14 Valid Valid Invalid Valid Multi-segment speed 13 F08.12 15 Valid Valid Valid Invalid Multi-segment F08.13