User Manual of EM730 Series Inverter Agent password. ★ After this password is set, the inverter may fail to work normally. Be careful to set this password. or exceeds the total cumulative power-on time (F16.07), please contact the agent for Set the total cumulative power-on time. If the cumulative power-on time (F12.15) reaches maintenance. ★ After this parameter is set, the inverter may fail to work normally. Be careful to set this parameter. exceeds the total cumulative running time (F16.08), please contact the agent for maintenance. Set the total cumulative running time.
If the cumulative running time (F12.17) reaches or ★ After this parameter is set, the inverter may fail to work normally. Be careful to set this parameter. Factory password. ★ After this password is set, the inverter may fail to work normally. Be careful to set this password. 308 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F16.07 Setting of cumulative power-on arrival time 0~65535; 0: disable the protection when the power-on time is up h 0 〇 0x1007 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F16.08 Setting of cumulative running arrival time 0~65535; 0:
disable the protection when the running time is up h 0 〇 0x1008 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F16.09 Factory password 0~ 65535 XXXXX ● 0x1009 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F16.10 Analog output percentage corresponding to 0.00~100.00 % 0.00 〇 0x100A