User Manual of EM730 Series Inverter 6.2 Table of functional parameters 71 Attribute Change attribute of the function code (permission and condition of change), as described below: ● Changeable in running: The current function code can be changed in any status. 〇 Non-changeable in running: The current function code can be changed except in the running status. × Read-only: The current function code cannot be changed in any status. Function code Function code name Parameter description Unit Defau lt setting Attri but e mailing address F00 Basic function parameter group F00.00 Reserved F00.01 Drive control mode of motor 1 0: v/f control (VVF) 1:
speed sensorless vector control (SVC) 0 〇 0x0001 F00.02 Options of command source 0: keyboard control (LOC/REM indicator: ON) 1: terminal control (LOC/REM indicator: OFF) 2: communication control (LOC/REM indicator: flicker) 0 〇 0x0002 F00.03 Options of terminal control mode 0: terminal RUN (running) and F/R (forward/reverse) 1: terminal RUN (forward) and F/R (reverse) 2: terminal RUN (forward), Xi (stop) and F/R (reverse) 3: terminal RUN (running), Xi (stop) and F/R (forward/reverse) 0 〇 0x0003 F00.04 Options of main frequency source A 0: digital frequency setting F00.07 1:AI1 2:AI2 3:reserved 4:reserved 5: high frequency pulse input (X5) 6:
main frequency communication setting (percentage) 7: main frequency communication setting (direct frequency) 8: digital potentiometer setting 8 〇 0x0004 F00.05 Options of auxiliary 0: digital frequency setting F00.07 1:AI1 0 〇 0x0005