User Manual of EM730 Series Inverter 88 stop F04.27 Second confirmation of terminal start command 0: Not required for confirmation 1: to be confirmed 2: Not required for confirmation of mode 2(also not required during fault reset) 0 〇 0x041B F04.28 Lowest effective output frequency 0.00~50.00(0.00:function invalid) Hz 0.00 〇 0x041C F04.29 Zero speed check frequency 0.00 ~ 5.00 Hz 0.25 ● 0x041D F04.30 Initial magnetic pole search mode of synchronous motor 0: Invalid 1: Mode 1 0 ● 0x041E F05 V/F control parameter group F05.00 V/F curve setting 0: straight line V/F 1: multi-point broken line V/F 2: 1.3-power V/F 3: 1.7-power V/F 4: square V/F 5:
vf complete separation mode (Ud = 0, Uq = K * t = voltage of separation voltage source) 6: vf semi-separation mode (Ud = 0, Uq = K * t = F/Fe * 2 * voltage of separation voltage source) 0 〇 0x0500 F05.01 Frequency point F1 of multi-point VF 0.00 ~ F05.03 Hz 0.50 ● 0x0501 F05.02 Voltage point V1 of multi-point VF 0.0~100.0 (100.0 = Rated voltage) % 1.0 ● 0x0502 F05.03 Frequency point F2 of multi-point VF F05.01~F05.05 Hz 2.00 ● 0x0503