User Manual of EM730 Series Inverter 89 F05.04 Voltage point V2 of multi-point VF 0.0~100.0 % 4.0 ● 0x0504 F05.05 Frequency point F3 of multi-point VF F05.03 to rated frequency of motor (reference frequency) Hz 5.00 ● 0x0505 F05.06 Voltage point V3 of multi-point VF 0.0~100.0 % 10.0 ● 0x0506 F05.07 Voltage source of VF separation mode 0: digital setting of VF separation voltage 1:AI1 2:AI2 4: high-frequency pulse (X5) 5:PID 6: communication setting note: 100% is the rated voltage of the motor.
0 〇 0x0507 F05.08 Digital setting of VF separation voltage 0.0~100.0 (100.0 = rated voltage of motor) % 0.0 ● 0x0508 F05.09 Rise time of VF separation voltage 0.00 ~ 60.00 s 2.00 ● 0x0509 F05.10 Compensation gain of V/F stator voltage drop 0.00 ~ 200.00 % 100.0 0 ● 0x050A F05.11 V/F slip compensation gain 0.00 ~ 200.00 % 100.0 0 ● 0x050B F05.12 V/F slip filtering time 0.00 ~ 10.00 s 1.00 ● 0x050C F05.13 Oscillation suppression gain 0 ~ 10000 100 ● 0x050D F05.14 Oscillation suppression cutoff frequency 0.00~600.00 Hz 55.00 ● 0x050E F05.15 Droop control frequency 0.00 ~ 10.00 Hz 0.00 ● 0x050F