sinee — 6.2Table of functional parameters

User Manual of EM730 Series Inverter 96 F06.78 Slip gain switching frequency of asynchronous motor 0.10 ~ Fmax Hz 5.00 〇 0x064D F06.82 Udc filtering time constant 0~1500.0 ms 2.0 ● 0x0652 F07 Protection function setting group F07.00 Protection shield E20 * E13 E06 * E04 E07 E 0 8 0*0 0*000 〇 0x0700 0: valid protection 1: shielded protection F07.01 Motor overload protection gain 0.20 ~ 10.00 1.00 ● 0x0701 F07.02 Motor overload pre-alarm coefficient 50 ~ 100 % 80 ● 0x0702 F07.06 Bus voltage control options Ones place: instantaneous stop/no-stop function options 0: invalid 1: deceleration 2: deceleration to stop Tens place: overvoltage stall function options 0: invalid 1:

valid 10 〇 0x0706 F07.07 Voltage of overvoltage stall control 110.0 ~ 150.0 (380V, 100.0=537V) % 131.0 (703V) 〇 0x0707 F07.08 Instantaneous stop/no-stop operating voltage 60.0 to instantaneous stop/no-stop recovery voltage (100.0 = standard bus voltage) % 76.0 〇 0x0708 F07.09 Instantaneous stop/no-stop recovery voltage instantaneous stop/no-stop operating voltage to 100.0 % 86.0 ● 0x0709