sinee — 10.3.4 Register address distribution

User Manual of EM760 High-Performance Inverter 263 Others to 00FFH Reserved 7001H Communication percentage setting of main channel frequency A -100.00% to 100.00% (100% = maximum frequency) 7002H Communication percentage setting of auxiliary channel frequency B -100.00% to 100.00% (100% = maximum frequency) 7003H Torque communication setting -200.00% to 200.00% (100% = digital torque setting) 7004H Communication setting ofprocess PID setting -100.00%~100.00% 7005H Communication setting of process PID feedback -100.00%~100.00% 7006H Voltage setting of VF separation mode 0.00% to 100.00% (digital setting reference) 7007H~7009H Reserved 700AH Communication percentage setting of upper frequency limit 0.00% to 200.00% (digital setting reference) 700BH Communication percentage setting of upper frequency limit of torque control 0.00% to 200.00% (digital setting reference) 700CH Linear speed input for inertia compensation 0.00% to 100.00% (digital setting reference) 700DH~700EH Reserved 700FH Master-slave communication setting -100.00% to 100.00% (maximum reference) 7010H~7013H Reserved 7014H External protection Protection input of external device (including option card) 7015H Communication setting of main channel frequency A 0.00 to maximum frequency 7016H Communication setting of auxiliary channel frequency B 0.00 to maximum frequency 7017H Communication setting of upper frequency limit 0.00 to maximum frequency 7018H Communication setting of upper frequency limit of torque control 0.00 to maximum frequency