User Manual of EM760 High-Performance Inverter 264 7019H Communication setting ofupper torque limit of speed control 0.0 to 250.0% (based on 100.0% or direct sending) 701AH Communication setting 1 Communication setting by M1 terminal, communication address option 701AH 701CH~71FFH Reserved Working status 7200H - 73FFH 7200H status word 1 Bit7 to 0 running status 00H Parameter setting 01H Slave running 02H JOG running 03H Self-learning running 04H Slave stop 05H JOG stop 06H Protection status 07H Factory self-inspection 08H~0FFH Reserved Bit15-8 protection information 00H Normal running of inverter xxH Inverter protection status, where “xx” is the protection code 7201H status word 2 Bit0 setting direction 1 - setting is valid 0 + setting is valid Bit1 running direction 1 Reverse frequency output 0 Forward frequency output Bit3 to 2 running mode 00 Speed control mode 01 Torque control mode 10 Reserved 11 Reserved Bit4 parameter protection 1 Valid parameter protection 0 Invalid parameter protection Bit6~5 Reserved Bit8 to 7 setting mode 00 Keyboard control 01 Terminal control 10 Communication control