User Manual of EM760 High-Performance Inverter 297 F05.09 Rise time of VF separation voltage 0.00~60.00 s 2.00 ● 0x0509 F05.10 Compensation gain of V/F stator voltage drop 0.00~200.00 % 100.00 ● 0x050A F05.11 V/F slip compensation gain 0.00~200.00 % 100.00 ● 0x050B F05.12 V/F slip filtering time 0.00~10.00 s 1.00 ● 0x050C F05.13 Oscillation suppression gain 0~20000 300 ● 0x050D F05.14 Oscillation suppression cutoff frequency 0.00~600.00 Hz 55.00 ● 0x050E F05.15 Droop control frequency 0.00~10.00 Hz 0.00 ● 0x050F F05.16 Energy saving rate 0.00~50.00 % 0.00 ● 0x0510 F05.17 Energy saving action time 1.00~60.00 s 5.00 ● 0x0511 F05.18 Flux compensation gain ofsynchronous motor 0.00~500.00 % 100.00 ● 0x0512 F05.19 Filtering time constant of flux compensation of synchronous motor 0.00~10.00 s 0.50 ● 0x0513 F05.20 Change rate of VF separate power supply setting –50.00~50.00 % 0.00 ● 0x0514 F06 Vector control parameter group F06.00 Speed proportional gain ASR P1 _ 0.00~100.00 12.00 ● 0x0600 F06.01 Speed integral time constant ASR T1 _ 0.000~30.000 0.000:
no integral s 0.250 ● 0x0601 F06.02 Speed proportional gain ASR P2 _ 0.00~100.00 10.00 ● 0x0602 F06.03 Speed integral time constant 0.000~30.000 s 0.300 ● 0x0603