User Manual of EM760 High-Performance Inverter 296 1: multi-point broken line V/F 2: 1.3-power V/F 3: 1.7-power V/F 4: square V/F 5: VF complete separation mode (Ud = 0,Uq = K * t = voltage of separation voltage source) 6:
VF semi-separation mode (Ud = 0, Uq = K * t = F/Fe * 2 * voltage of separation voltage source) F05.01 Frequency point F1 ofmulti-point VF 0.00~F05.03 Hz 0.50 ● 0x0501 F05.02 Voltage point V1 of multi-point VF 0.0~100.0 (100.0 = Rated voltage) % 1.0 ● 0x0502 F05.03 Frequency point F2 ofmulti-point VF F05.01~F05.05 Hz 2.00 ● 0x0503 F05.04 Voltage point V2 of multi-point VF 0.0~100.0 % 4.0 ● 0x0504 F05.05 Frequency point F3 ofmulti-point VF F05.03 to rated frequency of motor (reference frequency) Hz 5.00 ● 0x0505 F05.06 Voltage point V3 of multi-point VF 0.0~100.0 % 10.0 ● 0x0506 F05.07 Voltage source of VF separation mode 0: digital setting of VF separation voltage 1: AI1 2: AI2 3: AI3 4:
high frequency pulse (X7) 5: PID 6: Communication setting Note: 100% is the rated voltage of the motor. 0 O 0x0507 F05.08 Digital setting of VF separation voltage 0.0 to 100.0 (100.0=Rated voltage ofmotor) % 0.0 ● 0x0508