sinee — Chapter 11 Function Code Table

User Manual of EM760 High-Performance Inverter 302 F06.61 Current setting for self-learning at the initial position 0.10~1.25 0.90 O 0x063D F06.62 Speed ring proportion for rotation self- learning 0.00~100.00 2.00 O 0x063E F06.63 Speed ring integral time for rotation self-learning 0.000~30.000 s 0.150 O 0x063F F06.64 Acceleration time for rotation self- learning 5.00~100.00 s 20.00 O 0x0640 F06.65 Deceleration time for rotation self- learning 5.00~100.00 s 20.00 O 0x0641 F06.66 Asynchronous motor type selection 0: Built-in permanent magnet synchronous motor 1: Surface-mounted permanent magnet synchronous motor 2:

Permanent magnet direct drive motor 0 O 0x0642 F06.67 Excitation current MTPA calculation gain 0.0~300.0 % 20.0 ● 0x0643 F06.68 Excitation current flux weakening calculation gain 0.0~300.0 % 20.0 ● 0x0644 F06.69 Start compensation angle 0~360 ° 0 O 0x0645 F06.70 Expanded counter electrodynamic potential filtering factor 1 0.000~1.732 0.279 ● 0x0646 F06.71 Expanded counter electrodynamic potential filtering factor 2 0.000~1.732 0.578 ● 0x0647 F06.72 Minimum estimated frequency of synchronous motor SVC 0.01~100.00 HZ 0.50 O 0x0648 F06.73 Low frequency band ID-specific gain 0~500.0 % 100.0 ● 0x0649 F06.74 Smooth switching times 1~1000 20 ● 0x064A F06.75 Speed toggle-hold times 1~2000 100 ● 0x064B F06.76 Low-speed correction factor of stator resistor of asynchronous motor 10.0~500.0 % 100.0 ● 0x064C