User Manual of EM760 High-Performance Inverter 306 F07.39 Delay time of electrification reading and determination 0~100.0 S 5.00 O 0x0727 F07.40 Delay time of steady undervoltage determination 50~6000 ms 20 O 0x0728 F07.41 Selection of input phase loss detection method 0: Software detection 1: Hardware detection 2: Simultaneous software and hardware detection 0 O 0x0729 F07.42 Setting value of current for determining short to ground 0.00~100.0 % 20.0 O 0x072A F07.43 Warning shield * * * * * C32 C31 C30 0: Warning valid 1:
Warning shielded 00000000 O 0x072B F07.44 Upper limit of current for output phase loss detection 10.0~100.0 % 30.0 O 0x072C F07.45 Times of output phase loss detection 1~60000 10 O 0x072D F07.46 Times of determining ILP hardware detection 5~10000 100 ● 0x072E F07.47 Soft start disconnection delay time 20~1000 mS 400 O 0x072F F07.50 STO fault resetting 0: manual resetting 1: automatic resetting 0 O 0x0732 F08 Multi-segment speed and simple PLC F08.00 Multi-segment speed 1 0.00 to maximum frequency F00.16 Hz 0.00 ● 0x0800 F08.01 Multi-segment speed 2 0.00 to maximum frequency F00.16 Hz 5.00 ● 0x0801 F08.02 Multi-segment speed 3 0.00 to maximum frequency F00.16 Hz 10.00 ● 0x0802