User Manual of EM760 High-Performance Inverter Two-line control: F00.03=0: the terminal RUN is enabled and the terminal F/R controls forward/reverse running. The terminal RUN is activated/deactivated to control the start and stop of the inverter; terminal F/R is activated/deactivated to control the forward/reverse running. The logic diagram is shown in the figure (b) below; F00.03=1: the terminal RUN controls forward running, and the terminal F/R is in the reverse mode. Enable/Disable the terminal RUN to control the forward running and stop of the inverter, and the terminal F/R to control the reverse running and stop.
When the terminals RUN and F/Rare enabled simultaneously, the inverter will be stopped. When the mode of deceleration to stop is selected, the forward/reverse logic is as shown in the figure (d) below; (a) Wiring diagram of two-line control (F00.03=0) (b) F04.09=0, F00.03=0,run the forward/reverse logic (c) Wiring diagram of two-line control (F00.03=1) (d) F04.19=0, F00.03=1,run the forward/reverse logic Fig. 5-2 Two-line control Three-line control: F00.03=2: terminal RUN (forward), Xi (stop) and F/R (reverse) The terminal RUN is normally ON for forward running, and the terminal F/R is normally ON for reverse running, with valid pulse edges.
The terminal Xi is normally closed for stop, with the valid level. When the inverter is in the running status, press Xi to stop it. When the mode of deceleration to stop (F04.19=0) is selected, the logic is as shown in figure (b) below. Xi is the terminal among X1~X7 that is defined by F02.00~F02.06 for “three-line running and stop control”; 68