User Manual of EM760 High-Performance Inverter Note: X7 is high-speed pulse input; the supported frequency is 200kHz. F00.03=3: the terminal RUN is for running, Xi for stop and F/R for forward/reverse control. The terminal RUN is normally ON for running, with the valid pulse edge, F/R for forward/reverse switching (forward in the OFF status and reverse in the ON status), and Xi is normally OFF for stop, with the valid level. When the mode of deceleration to stop (F04.19=0) is selected, the logic diagram is as shown in figure (d) below. (a) Wiring diagram of three-line control (F00.03=2) (b) F04.19=0, F00.03=2:
forward/reverse running logic (c) Wiring diagram of three-line control (F00.03=3) (d) F04.19=0, F00.03=3: forward/reverse running logic Fig. 5-3 Three-line control 5.6 Common Process Parameters of Inverter 69 Function code Function codename Parameter description Unit Default setting Attribute F00.01 Drive control mode of motor 1 0: V/F control (VVF) 1: Speed sensorless vector control (SVC) 2: Speed sensor vector control (FVC) 0 〇 F00.04 Options of main frequency source A 0: digital frequency setting F00.07 1: AI1 2: AI2 3: AI3 4: AI4 (expansion card) 5: high frequency pulse input (X7) 6: Percentage setting of main frequency communication 7: Direct setting of main frequency communication 0 〇